HSC Physics · Module 6 · Electromagnetism · 14 min read
Transformers
A transformer changes the size of an alternating voltage. Phone chargers step 230 V down to a few volts; the grid steps a power station's output up to hundreds of thousands of volts and back down again before it reaches your home. Every one of them works by electromagnetic induction.
HSC questions on transformers are some of the most reliable marks in Module 6: a turns-ratio calculation, an explanation of where a real transformer loses energy, or a power-line question built on Ploss = I2R. This guide covers all three, then works a full transmission question. For flux, Faraday's law and Lenz's law themselves, see the electromagnetic induction guide.
What you need to know
- Calculate voltages, currents and turns in an ideal transformer with Vp/Vs = Np/Ns and VpIp = VsIs.
- Explain, in words, why a real transformer falls short of the ideal (flux that misses the secondary, eddy currents in the core, heating in the windings) and the design choices that cut each loss.
- Analyse where step-up and step-down transformers are used, especially in sending electricity over long distances at high voltage.
The equations (from the 2019 HSC data sheet unless marked):
Dot points: PH-M6-10, PH-M6-11, PH-M6-12 (2017 Physics syllabus, HSC 2026 and 2027), in our own words.
Mini lesson
How a transformer works
A transformer is two coils of insulated wire, the primary and the secondary, wound on one shared iron core. They are not electrically connected. An alternating current in the primary makes a magnetic flux in the core that keeps changing size and direction.
The core carries that changing flux through the secondary coil, and by Faraday's law a changing flux induces an emf in the secondary. This is why a transformer needs AC: a steady direct current makes a steady flux, and a steady flux induces nothing.
The output is AC at the same frequency as the input. Only the voltage and current change.
The turns ratio: step-up and step-down
Each turn of either coil links almost the same changing flux, so each turn has the same emf. The voltage on each side is therefore proportional to its number of turns: Vp/Vs = Np/Ns.
If the secondary has more turns than the primary, Vs is bigger than Vp: a step-up transformer. If it has fewer turns, it is a step-down transformer. A transformer with 50 primary turns and 1000 secondary turns steps up by a factor of 20; turned around, the same transformer steps down by 20.
- Step-up: Ns > Np, so Vs > Vp and Is < Ip.
- Step-down: Ns < Np, so Vs < Vp and Is > Ip.
- Write the ratio with p on top on both sides, then substitute. Most mistakes come from flipping one side.
Power in equals power out
An ideal transformer wastes no energy, so the power delivered to the primary equals the power delivered by the secondary: VpIp = VsIs. A transformer cannot make energy. If it steps the voltage up by 20 times, the current on the secondary side is 20 times smaller.
The secondary current is set by what is plugged in (the load), and the primary current follows it. Connect more appliances in parallel to the secondary and the total resistance falls, so the secondary current and the output power rise. To supply that power, the primary current must rise too. With nothing connected, an ideal transformer draws almost no current at all.
Real transformers: where the energy goes
Real transformers are very efficient (large ones reach about 99%), but some energy is always lost, mostly as heat. A question that asks how a design is made more efficient wants each feature linked to the loss it reduces:
- Flux leakage (partial flux linkage). Some of the primary's flux never passes through the secondary, so the secondary voltage is a little lower than the turns ratio predicts. Fix: wind both coils on a closed, soft-iron core, often one on top of the other, so almost all the flux links both coils.
- Eddy currents in the core. The changing flux induces currents in the iron core itself, which heat it. Fix: build the core from thin, insulated sheets (laminations). The insulation breaks up the current loops, so the eddy currents are much smaller and so is the heating. They are reduced, not removed.
- Resistive heating in the coils. The windings have resistance, so the currents in them make heat (I2R). Fix: use thick, low-resistance copper wire, especially for the high-current coil.
- Magnetising the core back and forth. Reversing the core's magnetism every cycle takes energy (hysteresis). Fix: use soft iron, which is easy to magnetise and demagnetise.
Why power lines run at high voltage
A power line has resistance, so the current in it heats the wire: Ploss = I2R. For a fixed amount of power, P = VI, so a higher voltage means a smaller current. Because the loss depends on the current squared, raising the voltage by 10 times cuts the current to a tenth and the line loss to a hundredth.
So the grid uses a step-up transformer at the power station, sends the energy over long distances at very high voltage, then uses step-down transformers in stages (substations, then the pole or street transformer) to bring it to 230 V for homes. Transformers are also why the grid is AC: a transformer changes an AC voltage easily, but it cannot change a DC voltage, and when the grid was built there was no practical way to do that.
Common mistakes
- Writing Vp/Vs = Ns/Np (one side flipped), so a step-down transformer comes out stepping up.Keep the primary on top on both sides: Vp/Vs = Np/Ns. Then check: more secondary turns must give a higher secondary voltage.
- Thinking a step-up transformer gives you more power because the voltage is higher.At best power out equals power in. A higher secondary voltage always comes with a smaller secondary current.
- Finding the line loss with V2/R, using the transmission voltage.The transmission voltage is not the voltage across the line's resistance. Find the line current with I = P ÷ V, then Ploss = I2R.
- Saying 'high voltage reduces energy loss' and stopping there.Give the chain: same power at a higher voltage → smaller current (P = VI) → much smaller heating, because Ploss = I2R depends on the current squared.
- Writing 'flux leakage' as a design feature, or listing losses without saying how each is reduced.Flux leakage is the loss. The fix is better flux linkage (a shared, closed soft-iron core). Pair every feature with the loss it reduces.
- Thinking the primary current is fixed, whatever is connected to the secondary.The load sets the secondary current, and VpIp = VsIs means a bigger load draws a bigger primary current.
Mini quiz
6 quick questions. Pick an answer to see if you're right and why.
-
Vs = Vp × Ns/Np = 230 × 2400 ÷ 400 = 1380 V. The secondary has 6 times the turns, so 6 times the voltage. 38 V comes from using the ratio upside down.
Show answer
C. Vs = Vp × Ns/Np = 230 × 2400 ÷ 400 = 1380 V. The secondary has 6 times the turns, so 6 times the voltage. 38 V comes from using the ratio upside down.
-
Pout = 19 × 3.4 = 64.6 W. With 90% efficiency, Pin = 64.6 ÷ 0.90 = 71.8 W, so Ip = 71.8 ÷ 230 = 0.31 A. 0.28 A is the ideal answer; 0.25 A multiplies by 0.90 instead of dividing; 41 A uses the voltage ratio the wrong way round.
Show answer
C. Pout = 19 × 3.4 = 64.6 W. With 90% efficiency, Pin = 64.6 ÷ 0.90 = 71.8 W, so Ip = 71.8 ÷ 230 = 0.31 A. 0.28 A is the ideal answer; 0.25 A multiplies by 0.90 instead of dividing; 41 A uses the voltage ratio the wrong way round.
-
More lamps in parallel lower the resistance of the load, so the secondary current and the output power rise. Power in must match power out (VpIp = VsIs), so the primary current rises too. The turns ratio fixes the voltages, not the currents.
Show answer
C. More lamps in parallel lower the resistance of the load, so the secondary current and the output power rise. Power in must match power out (VpIp = VsIs), so the primary current rises too. The turns ratio fixes the voltages, not the currents.
-
A closed soft-iron core shared by both coils guides almost all the primary's flux through the secondary. Laminations are a real improvement, but they reduce eddy currents, not flux leakage. Thinner wire increases resistive heating, and an air core links far less flux.
Show answer
B. A closed soft-iron core shared by both coils guides almost all the primary's flux through the secondary. Laminations are a real improvement, but they reduce eddy currents, not flux leakage. Thinner wire increases resistive heating, and an air core links far less flux.
-
Ploss = I2R = 502 × 2.0 = 5000 W = 5.0 kW. 1.0 MW is VI, the power being sent, not the loss. 200 MW comes from V2/R with the line voltage, which is not the voltage across the line's resistance.
Show answer
B. Ploss = I2R = 502 × 2.0 = 5000 W = 5.0 kW. 1.0 MW is VI, the power being sent, not the loss. 200 MW comes from V2/R with the line voltage, which is not the voltage across the line's resistance.
-
Induction needs a changing flux. A battery's steady DC makes a constant flux in the core, so the secondary has no emf, apart from a brief pulse at switch-on and switch-off. The coils are not connected through the core.
Show answer
B. Induction needs a changing flux. A battery's steady DC makes a constant flux in the core, so the secondary has no emf, apart from a brief pulse at switch-on and switch-off. The coils are not connected through the core.
Want more like these? Try five more on Transformers, marked as you go. Free, no account needed.
Worked example
A wind farm generates 6.0 MW of electrical power at 690 V AC. An ideal step-up transformer with a turns ratio Np : Ns = 1 : 48 feeds a 25 km line to a town. The total resistance of the line (both wires) is 4.0 Ω.
(a) Calculate the voltage and the current in the line. (2 marks)
(b) Calculate the power lost as heat in the line, as a value and as a percentage of the power generated. (2 marks)
(c) Without the transformer, the farm would send the same power along the same line at 690 V. Use your answers to explain why this would not work. (2 marks)
(6 marks)
I'll think out loud, the way you should in the exam, using KNOW-UD: Knowns, Not known, Organise, Work it out, Units, Direction.
Prediction first. Stepping 690 V up by 48 gives roughly 700 × 50 ≈ 35 kV. Then 6 MW ÷ 35 kV is somewhere near 200 A, and 2002 × 4 is about 160 kW, a few per cent of 6 MW. I predict a line current of about 200 A and a loss of the order of 100 kW, under 5%.
K · Knowns
I sketch the chain from farm to town and put every value on it. The line resistance is the total for both wires, so I use 4.0 Ω as it is. The transformer is ideal, so the power going into the line is the full 6.0 MW.
- P = 6.0 × 106 W, Vp = 690 V
- Np : Ns = 1 : 48, so Ns/Np = 48
- Rline = 4.0 Ω
N · Not known
Part (a) wants two numbers, (b) wants a power and a percentage, and (c) wants a reason backed by numbers. The line current is the key quantity: the loss depends on it.
- (a) Vs = ? V, Iline = ? A
- (b) Ploss = ? W, and Ploss as a % of 6.0 MW
- (c) the line current and loss at 690 V, and what they mean
O · Organise
I write the equations in symbols first. The secondary voltage comes from the turns ratio. The line current comes from P = VI on the secondary side, because the transformer is ideal. The loss is I2R with the line's resistance, never V2/R with the transmission voltage.
- Vs = Vp × Ns/Np
- Iline = P ÷ Vs
- Ploss = Iline2 Rline
W · Work it out
I keep the full calculator value of the current, because it gets squared next. For (c) I could redo the whole calculation, but there's a quicker route: the current would be 48 times bigger, so the loss would be 482 times bigger. I'll do both as a check.
- (a) Vs = 690 × 48 = 33 120 V
- Iline = 6.0 × 106 ÷ 33 120 = 181.16 A
- (b) Ploss = 181.162 × 4.0 = 1.3127 × 105 W
- % lost = 1.3127 × 105 ÷ 6.0 × 106 × 100 = 2.19%
- (c) At 690 V: I = 6.0 × 106 ÷ 690 = 8695.7 A
- Ploss = 8695.72 × 4.0 = 3.02 × 108 W (check: 482 × 1.3127 × 105 = 3.02 × 108 W)
U · Units
Volts times a pure ratio is volts; watts over volts is amps; amps squared times ohms is watts. The data are given to two significant figures, so I round to two or three.
- (a) Vs ≈ 33 kV (3.3 × 104 V), Iline ≈ 180 A
- (b) Ploss ≈ 1.3 × 105 W = 0.13 MW, about 2.2% of the power generated
- (c) at 690 V the line current would be about 8.7 × 103 A and the calculated loss about 3.0 × 108 W
D · Direction
These are scalars, so I finish with a sense check and the explanation for (c). The 690 V loss of 300 MW is fifty times the 6 MW the farm makes, which is impossible: it tells me the line simply cannot carry the power at that voltage. Almost all of the 690 V would be dropped across the line itself (8696 A × 4.0 Ω is far more than 690 V), so nothing useful would reach the town.
- (c) For the same power, sending at 690 V instead of 33 kV makes the current 48 times larger. The heating in the line depends on I2, so the loss would be 482 ≈ 2300 times larger: about 3 × 108 W, far more than the 6.0 MW generated. So essentially none of the energy would reach the town; stepping up the voltage cuts the current and keeps the line loss to about 2%.
(a) The line runs at about 33 kV (33 120 V) with a current of about 180 A. (b) About 1.3 × 105 W (0.13 MW) is lost in the line, about 2.2% of the power generated. (c) At 690 V the current would be 48 times larger and the I2R loss about 2300 times larger (about 3 × 108 W), more than the farm generates, so the power could not be delivered.
Check against the prediction. I predicted a line current near 200 A and a loss of the order of 100 kW, under 5%. The answers are 180 A and 130 kW (2.2%), so they fit. My estimate rounded the current up to 200 A, and that error is squared in the loss, which is why it came out a bit high.
Prefer to watch one worked? Watch a narrated worked example in the app.
HSC advice
What markers keep saying
- Set out transformer calculations in full: the equation, the substitution, then the answer with its unit. Markers can only give method marks for working they can see.NESA marking feedback, 2023, summarised
- When a transformer's measured output power is less than its input, say what happened to the difference: it was transferred out of the circuit, mostly as heat. Then name the cause.NESA marking feedback, 2019, summarised
- For efficiency questions, tie each design feature to one loss. Say that laminations reduce (not stop) eddy currents, and use the term flux linkage when you explain the shared iron core.NESA marking feedback, 2022, summarised
- If the load on the secondary increases, explain the effect on the primary current through conservation of energy: more power out needs more power in, so with Vp fixed, Ip rises.NESA marking feedback, 2023, summarised
- When a question asks about energy in a whole supply system, cover both parts: the losses inside the transformers and the I2R heating in the transmission lines. A general description of how a transformer works earns little on its own.NESA marking feedback, 2025, summarised
Summaries in our own words. Read NESA's own feedback with the exam packs: 2019 · 2022 · 2023 · 2025.
How often it is examined
Transformers questions were worth 69 marks across the seven HSC Physics exams from 2019 to 2025 (about 9.9 marks a paper), and appeared in 7 of 7 papers.
FAQ
- Are the transformer equations on the HSC data sheet?
- Yes. The 2019 data sheet gives Vp/Vs = Np/Ns and VpIp = VsIs. Ploss = I2R is not written there, but P = VI and V = IR are, and it follows from those two.
- What is the difference between a step-up and a step-down transformer?
- A step-up transformer has more turns on its secondary than its primary, so it raises the voltage and lowers the current. A step-down transformer has fewer secondary turns, so it lowers the voltage and raises the current. In both, power out is (ideally) equal to power in.
- Why are transformer cores laminated?
- The changing flux induces eddy currents in the iron core, which waste energy as heat. Making the core from thin sheets insulated from each other breaks up the current paths, so the eddy currents and the heating are much smaller. Laminations reduce eddy currents; they don't remove them.
- Does a step-up transformer increase power?
- No. An ideal transformer delivers exactly the power it takes in, and a real one delivers a little less. Raising the voltage lowers the current by the same factor, so the product VI does not go up.
- Why is electricity sent along power lines at high voltage?
- The heat lost in a line is Ploss = I2R. Sending the same power at a higher voltage needs a smaller current (P = VI), and because the loss depends on the current squared, it falls sharply. Ten times the voltage gives one hundredth of the loss.
Test yourself on this in 2 minutes
Five quick questions on Transformers in the CortexHSC app, marked as you go. Free, and no account needed.
Start the quick checkRelated guides
Explore more of CortexHSC
CortexHSC is a HSC Physics study app, free to start: learn every dot point, find and fix your mistakes, and practise with feedback. Pick up where this guide leaves off:
- Smart RevisePractice questions picked from what you got wrong last time, with the data sheet built in.
- Palm cardsFormulas and definitions as quick-recall cards, spaced so they stick.
- Practice papersFull HSC-style papers built from HSC patterns. One full AI-marked attempt is free with an account.
- AI markingWrite a full answer and get a mark and feedback against marking notes in seconds.
- VideosShort narrated lessons and think-aloud worked examples.
- PlannerPlan study around school, work and assessments, and keep your streak going.
Free to start, no card needed. Some features need a free account; the rest open with a free trial or a school account.