CortexHSC

HSC Physics · Module 6 · Electromagnetism · 14 min read

Transformers

Written and checked by a NSW Physics teacher (15+ years) · Updated

A transformer changes the size of an alternating voltage. Phone chargers step 230 V down to a few volts; the grid steps a power station's output up to hundreds of thousands of volts and back down again before it reaches your home. Every one of them works by electromagnetic induction.

HSC questions on transformers are some of the most reliable marks in Module 6: a turns-ratio calculation, an explanation of where a real transformer loses energy, or a power-line question built on Ploss = I2R. This guide covers all three, then works a full transmission question. For flux, Faraday's law and Lenz's law themselves, see the electromagnetic induction guide.

What you need to know

The equations (from the 2019 HSC data sheet unless marked):

Vp/Vs = Np/NsIdeal transformer: the voltage ratio equals the turns ratio. More turns on the secondary means a higher secondary voltage (step-up).
VpIp = VsIsIdeal transformer: power in equals power out. Whatever factor the voltage goes up by, the current goes down by.
P = VI V = IROn the sheet. Use P = VI to find the current in a line, and combine them for the heating in the line.
Ploss = I2R not on the data sheetPower lost as heat in a line of resistance R carrying current I. Comes from P = VI with V = IR.
efficiency = Pout ÷ Pin × 100% not on the data sheetFor a real transformer, Pout is less than Pin; the difference is mostly heat.

Dot points: PH-M6-10, PH-M6-11, PH-M6-12 (2017 Physics syllabus, HSC 2026 and 2027), in our own words.

Mini lesson

How a transformer works

A transformer is two coils of insulated wire, the primary and the secondary, wound on one shared iron core. They are not electrically connected. An alternating current in the primary makes a magnetic flux in the core that keeps changing size and direction.

The core carries that changing flux through the secondary coil, and by Faraday's law a changing flux induces an emf in the secondary. This is why a transformer needs AC: a steady direct current makes a steady flux, and a steady flux induces nothing.

The output is AC at the same frequency as the input. Only the voltage and current change.

A transformer: a square iron core with a primary coil of a few turns on the left side, connected to an AC supply, and a secondary coil of more turns on the right side, connected to a load. Arrows around the core show the changing flux.~changing flux in the coreAC inloadprimary, Npsecondary, Ns
The primary (blue) makes a changing flux in the core (green). The core carries it through the secondary (orange), which has its own emf. This one has more secondary turns, so it is a step-up transformer.

The turns ratio: step-up and step-down

Each turn of either coil links almost the same changing flux, so each turn has the same emf. The voltage on each side is therefore proportional to its number of turns: Vp/Vs = Np/Ns.

If the secondary has more turns than the primary, Vs is bigger than Vp: a step-up transformer. If it has fewer turns, it is a step-down transformer. A transformer with 50 primary turns and 1000 secondary turns steps up by a factor of 20; turned around, the same transformer steps down by 20.

Power in equals power out

An ideal transformer wastes no energy, so the power delivered to the primary equals the power delivered by the secondary: VpIp = VsIs. A transformer cannot make energy. If it steps the voltage up by 20 times, the current on the secondary side is 20 times smaller.

The secondary current is set by what is plugged in (the load), and the primary current follows it. Connect more appliances in parallel to the secondary and the total resistance falls, so the secondary current and the output power rise. To supply that power, the primary current must rise too. With nothing connected, an ideal transformer draws almost no current at all.

Real transformers: where the energy goes

Real transformers are very efficient (large ones reach about 99%), but some energy is always lost, mostly as heat. A question that asks how a design is made more efficient wants each feature linked to the loss it reduces:

Two transformer cores side by side. The solid core on the left has large eddy-current loops spread across it. The laminated core on the right is split into thin insulated strips, each with only a small, narrow eddy-current loop.solid corelaminated corebig loops: large eddy currentsthin strips: small loops
Laminations: the insulated layers confine each eddy current to a thin strip, so the currents, and the heat they make in the core, are much smaller.

Why power lines run at high voltage

A power line has resistance, so the current in it heats the wire: Ploss = I2R. For a fixed amount of power, P = VI, so a higher voltage means a smaller current. Because the loss depends on the current squared, raising the voltage by 10 times cuts the current to a tenth and the line loss to a hundredth.

So the grid uses a step-up transformer at the power station, sends the energy over long distances at very high voltage, then uses step-down transformers in stages (substations, then the pole or street transformer) to bring it to 230 V for homes. Transformers are also why the grid is AC: a transformer changes an AC voltage easily, but it cannot change a DC voltage, and when the grid was built there was no practical way to do that.

Flow chart of the electricity grid: the generator at tens of kilovolts feeds a step-up transformer, a transmission line at hundreds of kilovolts with a small current, then step-down transformers in stages, and finally homes at 230 volts.generatorstep-upstep-downhomestens of kVtransmissionline: hundredsof kV, small I230 Vin stages
Step up at the power station, transmit at high voltage and low current, step down near the users. The I2R loss in the long line is what the high voltage keeps small.

Common mistakes

Mini quiz

6 quick questions. Pick an answer to see if you're right and why.

  1. An ideal transformer has 400 turns on its primary and 2400 turns on its secondary. The primary is connected to 230 V AC. What is the secondary voltage?
    Show answer

    C. Vs = Vp × Ns/Np = 230 × 2400 ÷ 400 = 1380 V. The secondary has 6 times the turns, so 6 times the voltage. 38 V comes from using the ratio upside down.

  2. A laptop charger's transformer takes 230 V and supplies 19 V at 3.4 A. It is 90% efficient. What is the primary current?
    Show answer

    C. Pout = 19 × 3.4 = 64.6 W. With 90% efficiency, Pin = 64.6 ÷ 0.90 = 71.8 W, so Ip = 71.8 ÷ 230 = 0.31 A. 0.28 A is the ideal answer; 0.25 A multiplies by 0.90 instead of dividing; 41 A uses the voltage ratio the wrong way round.

  3. More lamps are connected in parallel to the secondary of a step-down transformer. What happens to the current in the primary?
    Show answer

    C. More lamps in parallel lower the resistance of the load, so the secondary current and the output power rise. Power in must match power out (VpIp = VsIs), so the primary current rises too. The turns ratio fixes the voltages, not the currents.

  4. Which change to a transformer's design mainly improves its flux linkage?
    Show answer

    B. A closed soft-iron core shared by both coils guides almost all the primary's flux through the secondary. Laminations are a real improvement, but they reduce eddy currents, not flux leakage. Thinner wire increases resistive heating, and an air core links far less flux.

  5. A transmission line of resistance 2.0 Ω carries a current of 50 A at 20 kV. How much power is lost as heat in the line?
    Show answer

    B. Ploss = I2R = 502 × 2.0 = 5000 W = 5.0 kW. 1.0 MW is VI, the power being sent, not the loss. 200 MW comes from V2/R with the line voltage, which is not the voltage across the line's resistance.

  6. Why does a transformer not work when its primary is connected to a battery?
    Show answer

    B. Induction needs a changing flux. A battery's steady DC makes a constant flux in the core, so the secondary has no emf, apart from a brief pulse at switch-on and switch-off. The coils are not connected through the core.

Want more like these? Try five more on Transformers, marked as you go. Free, no account needed.

Worked example

A wind farm generates 6.0 MW of electrical power at 690 V AC. An ideal step-up transformer with a turns ratio Np : Ns = 1 : 48 feeds a 25 km line to a town. The total resistance of the line (both wires) is 4.0 Ω.

(a) Calculate the voltage and the current in the line. (2 marks)

(b) Calculate the power lost as heat in the line, as a value and as a percentage of the power generated. (2 marks)

(c) Without the transformer, the farm would send the same power along the same line at 690 V. Use your answers to explain why this would not work. (2 marks)

(6 marks)

I'll think out loud, the way you should in the exam, using KNOW-UD: Knowns, Not known, Organise, Work it out, Units, Direction.

Prediction first. Stepping 690 V up by 48 gives roughly 700 × 50 ≈ 35 kV. Then 6 MW ÷ 35 kV is somewhere near 200 A, and 2002 × 4 is about 160 kW, a few per cent of 6 MW. I predict a line current of about 200 A and a loss of the order of 100 kW, under 5%.

K · Knowns

I sketch the chain from farm to town and put every value on it. The line resistance is the total for both wires, so I use 4.0 Ω as it is. The transformer is ideal, so the power going into the line is the full 6.0 MW.

  • P = 6.0 × 106 W, Vp = 690 V
  • Np : Ns = 1 : 48, so Ns/Np = 48
  • Rline = 4.0 Ω
Sketch of the system: a wind farm producing 6.0 megawatts at 690 volts feeds a 1 to 48 step-up transformer, then a 25 kilometre line of total resistance 4.0 ohms to a town. The line current and power loss are unknown.wind farm1 : 48townR = 4.0 Ω6.0 MW at 690 Vstep-upI = ?, Ploss = ?25 km line, total resistance 4.0 Ω (both wires)Np : Ns = 1 : 48, ideal transformer
Knowns on the sketch: 6.0 MW at 690 V, turns ratio 1 : 48, line resistance 4.0 Ω. Unknowns: the line voltage and current, and the power lost in the line.

N · Not known

Part (a) wants two numbers, (b) wants a power and a percentage, and (c) wants a reason backed by numbers. The line current is the key quantity: the loss depends on it.

  • (a) Vs = ? V, Iline = ? A
  • (b) Ploss = ? W, and Ploss as a % of 6.0 MW
  • (c) the line current and loss at 690 V, and what they mean

O · Organise

I write the equations in symbols first. The secondary voltage comes from the turns ratio. The line current comes from P = VI on the secondary side, because the transformer is ideal. The loss is I2R with the line's resistance, never V2/R with the transmission voltage.

  • Vs = Vp × Ns/Np
  • Iline = P ÷ Vs
  • Ploss = Iline2 Rline

W · Work it out

I keep the full calculator value of the current, because it gets squared next. For (c) I could redo the whole calculation, but there's a quicker route: the current would be 48 times bigger, so the loss would be 482 times bigger. I'll do both as a check.

  • (a) Vs = 690 × 48 = 33 120 V
  • Iline = 6.0 × 106 ÷ 33 120 = 181.16 A
  • (b) Ploss = 181.162 × 4.0 = 1.3127 × 105 W
  • % lost = 1.3127 × 105 ÷ 6.0 × 106 × 100 = 2.19%
  • (c) At 690 V: I = 6.0 × 106 ÷ 690 = 8695.7 A
  • Ploss = 8695.72 × 4.0 = 3.02 × 108 W (check: 482 × 1.3127 × 105 = 3.02 × 108 W)

U · Units

Volts times a pure ratio is volts; watts over volts is amps; amps squared times ohms is watts. The data are given to two significant figures, so I round to two or three.

  • (a) Vs ≈ 33 kV (3.3 × 104 V), Iline ≈ 180 A
  • (b) Ploss ≈ 1.3 × 105 W = 0.13 MW, about 2.2% of the power generated
  • (c) at 690 V the line current would be about 8.7 × 103 A and the calculated loss about 3.0 × 108 W

D · Direction

These are scalars, so I finish with a sense check and the explanation for (c). The 690 V loss of 300 MW is fifty times the 6 MW the farm makes, which is impossible: it tells me the line simply cannot carry the power at that voltage. Almost all of the 690 V would be dropped across the line itself (8696 A × 4.0 Ω is far more than 690 V), so nothing useful would reach the town.

  • (c) For the same power, sending at 690 V instead of 33 kV makes the current 48 times larger. The heating in the line depends on I2, so the loss would be 482 ≈ 2300 times larger: about 3 × 108 W, far more than the 6.0 MW generated. So essentially none of the energy would reach the town; stepping up the voltage cuts the current and keeps the line loss to about 2%.

(a) The line runs at about 33 kV (33 120 V) with a current of about 180 A. (b) About 1.3 × 105 W (0.13 MW) is lost in the line, about 2.2% of the power generated. (c) At 690 V the current would be 48 times larger and the I2R loss about 2300 times larger (about 3 × 108 W), more than the farm generates, so the power could not be delivered.

Check against the prediction. I predicted a line current near 200 A and a loss of the order of 100 kW, under 5%. The answers are 180 A and 130 kW (2.2%), so they fit. My estimate rounded the current up to 200 A, and that error is squared in the loss, which is why it came out a bit high.

Prefer to watch one worked? Watch a narrated worked example in the app.

HSC advice

What markers keep saying

Summaries in our own words. Read NESA's own feedback with the exam packs: 2019 · 2022 · 2023 · 2025.

How often it is examined

Transformers questions were worth 69 marks across the seven HSC Physics exams from 2019 to 2025 (about 9.9 marks a paper), and appeared in 7 of 7 papers.

1020195202011202111202214202310202482025
Marks per paper (Module 6, Electromagnetic Induction). Source: CortexHSC's own tagging of the NESA HSC Physics exams 2019–2025, each question counted under its main topic, so treat the numbers as close, not exact.
HSC Physics 2026: What 7 Years of Exams Show7:51 · CortexHSC on YouTube
Every HSC Physics paper from 2019 to 2025 and NESA's marking feedback: the shape of the paper and what keeps coming up. The video plays from YouTube once you press play.

FAQ

Are the transformer equations on the HSC data sheet?
Yes. The 2019 data sheet gives Vp/Vs = Np/Ns and VpIp = VsIs. Ploss = I2R is not written there, but P = VI and V = IR are, and it follows from those two.
What is the difference between a step-up and a step-down transformer?
A step-up transformer has more turns on its secondary than its primary, so it raises the voltage and lowers the current. A step-down transformer has fewer secondary turns, so it lowers the voltage and raises the current. In both, power out is (ideally) equal to power in.
Why are transformer cores laminated?
The changing flux induces eddy currents in the iron core, which waste energy as heat. Making the core from thin sheets insulated from each other breaks up the current paths, so the eddy currents and the heating are much smaller. Laminations reduce eddy currents; they don't remove them.
Does a step-up transformer increase power?
No. An ideal transformer delivers exactly the power it takes in, and a real one delivers a little less. Raising the voltage lowers the current by the same factor, so the product VI does not go up.
Why is electricity sent along power lines at high voltage?
The heat lost in a line is Ploss = I2R. Sending the same power at a higher voltage needs a smaller current (P = VI), and because the loss depends on the current squared, it falls sharply. Ten times the voltage gives one hundredth of the loss.

Test yourself on this in 2 minutes

Five quick questions on Transformers in the CortexHSC app, marked as you go. Free, and no account needed.

Start the quick check